2012/10/12

Round Cooling Tower ST Series


Categories: Cooling Tower
Brand:ANGES
Model:ST-30
Material:FRP
Cooling Type:Counter Flow
Flow Rate (m3/h):23.4
Motor(kw):0.75
Type Of Drive:direct


Detailed Info
ANGES cooling tower chassis features anti-corrosion,strong ability of resistance of bad weather and beautiful appearance,is made of high strength classfiber,and its rotation part and connection area is made of high quality raw materials,that greatly improve the servcie life and connection strength.


Technical data of cooling tower ST-8~ST-15

Model
ST
8
10
15
20
25
30
Data
Nominal Flow
 
6.23
7.81
11.7
15.62
19.51
23.4
Air Volume
CMM
70
85
140
160
200
230
Motor
KW
0.18
0.18
0.37
0.56
0.75
0.75
Noise Level(16M)
DBA
45.5
47
48
50
52
54
Dry Weight
KG
42
46
54
67
98
116
Wet Weight
KG
180
190
290
300
500
530
Piping
Water Inlet
WI
40
40
50
50
80
80
Water Outlet
WI
40
40
50
50
80
80
Overflow
OF
25
25
25
25
25
25
Drain
DR
25
25
25
25
25
25
Height
Tower
TH
1700
1830
1645
1930
2150
1895
Motor
MH
170
 
170
170
180
180
Casing
CH
940
1070
855
1140
1385
1130
Air Inlet
AH
170
170
170
170
245
245
Water Basin
WH
420
420
450
450
340
340
Water Inlet
IH
270
270
280
280
175
175
Water Outlet
OH
180
180
190
190
115
115
DIA.
Exhaust Fan
ED
550
635
635
770
770
770
Water Basin
WD
920
920
1165
1165
1385
1650
Anchor Bolt
BD
9*3 
9*3
9*3
9*3
9*3
9*3



Remarks:
1.parameter of design:in temp-T1=37°C,wet temp-WBT=27°C difference in temperature of water △Ts=5°C air pressure-P=99400Pa.
2.The above dimensions also apply to the ST series,LKT/SS stainless steel type and ST high temperature type.
3.Information subjected to change without prior notice.


KeyWords: